Function description
Chapter 3
OPERATION MANUAL
V1.2.0en/11.12.20//0.3.1
KISS Immersion Circulator
29
Designation
Specification
Calcium carbonate per liter
≤ 1.5 mmol/l; corresponds to a water hardness of: ≤ 8.4 °dH (soft)
PH value
between 6.0 and 8.5
Ultrapure water, distillates
Add 0.1 g of sodium carbonate (Na
2
CO
3
) per liter
Not approved water
Distilled, deionized, demineralized, chloric, ferruginous, ammoniacal, or
contaminated river water or sea water
Volume circulated (at least)
3 l/min.
Thermal fluid: Water without ethylene glycol
Use
≥ 0 °C
Thermal fluid: Water-ethylene glycol mixture
Use
< 0 °C
Thermal fluid composition
The mixture’s temperature must be 10 K below the permissible min. tem-
perature. For the permissible temperature range, refer to the datasheet
from page 58 in Section
.
For thermal fluids we recommend the media listed in the Huber catalog. The name of a thermal
fluid is
derived from its working temperature range and its viscosity at 25 °C.
3.3
To be noted when planning the test
Also observe page 13 in section
.
The focus is on your application. Bear in mind that system performance is influenced by heat trans-
fer, temperature, thermal fluid viscosity, volume flow, and flow speed.
▪
Make sure that the electrical connection is adequately dimensioned.
▪
The installation location of the temperature control unit should be selected so as to ensure ade-
quate fresh air, even with water-cooled chillers.
▪
Select the thermal fluid to be used in such a way that it not only permits the minimum and maxi-
mum working temperature but is also suitable with regard to fire point, boiling point, and viscosi-
ty. In addition, the thermal fluid must be compatible with all the materials in your system.
▪
Basically, you should only use the thermal fluid recommended by the manufacturer and only
within the usable temperature and pressure range.
▪
The application should be roughly at the same height of or below the temperature control unit if
the thermoregulation is close to the boiling temperature of the thermal fluid.
▪
Fill the temperature control unit slowly, carefully and evenly. Wear the necessary personal pro-
tective equipment, such as goggles, heat-proof and chemical-resistant gloves, etc.
For water-cooled temperature control units, please take the cooling water temperature necessary
for perfect operation and the required differential pressure from the data sheet from page 58
onward in the Section
.
Thermal fluid: Water
Summary of Contents for KISS 1 Series
Page 1: ...KISS Immersion Circulator...
Page 2: ......
Page 3: ...OPERATION MANUAL KISS Immersion Circulator...
Page 4: ......
Page 10: ...OPERATION MANUAL KISS Immersion Circulator V1 2 0en 11 12 20 0 3 1 10...