57
6 Routing Ground and Power Cables
N66B Cabinet Cabling
a
Do not install or remove power cables while
the equipment is powered on. Ensure that the
power is switched off prior to removing or
installing a power cable to avoid bodily
injuries.
CAUTION
Phillips
screwdriver
Adjustable wrench
Bind the power cables in a bundle, then route the
power and ground cables through the cable rack
above the cabinet.
At the top of the cabinet, connect the ground
cable to the ground screws. Then thread the
power cables into the cabinet through the cable
holes and connect them to the DC input terminals
on the PDU at the top of the cabinet.
Overhead Cabling
Underfloor Cabling
Thread power and ground cables into the cabinet
through cable holes in the ESD support at the
bottom of the cabinet. For the ground cable, route it
by way of the cable-routing area, thread it through
the cable hole at the top of the cabinet, and
connect it to the ground screws. For the power
cables, route them by way of the cable-routing area
to the top of the cabinet.
Ground cable
(yellow-green)
Cable-routing
area
M8 bolt