46
1 PDF Circuit Breaker
Installing/Routing Power Cables-DC
Cabinet
Scenario
PDU
PDF Circuit Breaker
N66B
1 x T64 s 2
x T32 subracks
DPD63-8-8
Configuration 1
: 16 x 63 A
Configuration 2
: 8 x 125 A
TN51PDU
1 x T64 s 4
x 6800 subracks
DPD63-8-8
Configuration 1
: 8 x 63 A (T64 subrack) + 8 x 32 A
(6800 subrack)
Configuration 2
: 4 x 125 A (T64 subrack) + 4 x 63 A
(6800 subrack)
TN51PDU
1 x T64 s 4 x
T16 subracks
DPD63-8-8
Configuration 1
: 16 x 63 A
Configuration 2
: 8 x 125 A
TN16PDU
1 x T64 s 4 x
universal platform
subracks
DPD63-8-8
Configuration 1
: 16 x 63 A
Configuration 2
: 8 x 125 A
NOTE
In configuration 1, DC PDUs are not equipped with copper fittings. In configuration 2, DC PDUs are equipped
with copper fittings. This NOTE applies globally.
Cabinet
Scenario
PDU
PDF Circuit Breaker
N63B-2m
1 x T32 s 1 x
T16 subrack
DPD63-8-8
Configuration 1
: 8 x 63 A
Configuration 2
: 4 x 125 A
TN16PDU
1 x T32 s 1 x
universal platform
subrack
DPD63-8-8
Configuration 1
: 8 x 63 A
Configuration 2
: 4 x 125 A
3 x T16 subrack s
DPD63-8-8
Configuration 1
: 8 x 63 A
Configuration 2
: 4 x 125 A
TN16PDU
2 x T16 su 1
x universal platform
subrack
DPD63-8-8
Configuration 1
: 8 x 63 A
Configuration 2
: 4 x 125 A
1 x T16 s 2 x
universal platform
subracks
DPD63-8-8
Configuration 1
: 8 x 63 A
Configuration 2
: 4 x 125 A
3 x universal platform
subracks
DPD63-8-8
Configuration 1
: 8 x 63 A
Configuration 2
: 4 x 125 A