55
5 Installing Power Cables Between the TN16PDU and PDF
TN16PDU Introduction
a
1
+
-
2
+
-
3
+
-
4
+
-
1
+
-
2
+
-
3
+
-
4
+
-
A
B
Installing Power Cables
b
Power supply
output area (A)
Power supply switch
area
Power supply
input area
Power supply
switch area
Power supply
output area (B)
Determine whether copper fittings need to be installed in the power input areas based on the site survey result.
NOTE
Do not install any copper fitting in the power output areas of the DC PDU. If copper fittings are required, install them only
in the power input areas of the DC PDU.
DANGER
Install the OT terminals correctly according to
the schematic wiring terminal labels on the
plastic cover of the DC power distribution box.
CAUTION
When installing power cables, use a
Phillips screwdriver or a straight shank
socket wrench to fasten screws. If
using a socket wrench to fasten
screws, you may break the screws.
CAUTION
TN16PDU
TN51PDU
Power supply
output area (A)
Power supply switch
area
Power supply
input area
Power supply
switch area
Power supply
output area (B)
The TN51PDU and TN16PDU just look differently. The methods of installing copper fittings, external power cables, and
subrack power cables are similar for them. The following uses the TN16PDU as an example to illustrate the installation.
NOTE