Figure 3-43 RS485 monitoring communications cable
(4) Blue
(5) White-and-blue
----End
3.6.4.2 Independent Networking Scenario
NO TE
Select one of the following networking modes according to the actual situation.
3.6.4.2.1 CAN Te RS485 Monitoring
Step 1 Connect teamwork and monitoring communications cables.
Networking
CAN Teamwork
RS485 Monitoring
Protocol
CAN
Modbus-RTU
Description
One teamwork network
supports a maximum of 32
units. On the Teamwork
Settings screen of the display
modules of the first and last
units, set Enable teamwork
CAN resistor to Yes.
It takes 3 x
n
seconds to
collect data from
n
units. If
the time required for the host
to collect data from all units
does not meet the
performance requirements,
group the units.
● If units are not grouped (
n
= 1), set RS485 monitoring
grouping to Enable on the
Modbus Settings screen
for each unit.
● If units are grouped (
n
> 1;
recommended:
n
≤ 4), set
RS485 monitoring
grouping to Enable on the
Modbus Settings screen
for the unit with the
COM/FE port connected.
Retain the default setting
(Disable) for other units.
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual