Parameter
Description
Hot aisle temperature
and humidity sharing
This function can be enabled only when at least one
smart cooling product in the group is equipped with
hot aisle T/H sensors. If this function is enabled, the
master unit in the teamwork group collects the hot
aisle temperature and humidity values from all units
equipped with hot aisle sensors, and synchronizes
the temperature and humidity values to all units
after logical calculation.
After this function is enabled, the master unit
synchronizes the temperature and humidity control
type and setpoints to all slave units.
Step 3 Complete the teamwork settings for all the smart cooling products by performing
Step 4 On the home screen of the display module of any teamwork controlled smart
cooling product, tap
. If the teamwork control succeeds, the teamwork
topology of the smart cooling product in the group is displayed.
Figure 4-5 Teamwork topology
No.
Item
Note
1
On/Off
● On: The device is started.
● Off: The device is shut down.
2
01/02/03...
Indicates the device address. The smallest
address is for the master unit and the rest are
for slave units.
If the master unit is offline, the online device
with the smallest address is selected to be the
new master.
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
4 Power-On Commissioning