Menu
Name
Parameter Description
Default Value
Settings >
System
Settings >
T/H sensor
Temperature and
humidity control
type
Cold aisle, Hot aisle,
Return air, or Supply air
can be set as required. The
temperature and humidity
set points correspond to
the selected control type
can be set.
Supply air
Temperature
control mode
Set the temperature inside
the room or aisles based
on the Average value,
Max value, or Min value
of the temperatures
collected by each sensor.
Average value
Temperature
setpoint
After the temperature and
humidity control type and
the temperature value
under this type are set, the
device performs cooling or
heating based on the
settings.
22.0°C
Humidity setpoint After the temperature and
humidity control type and
the humidity value under
this type are set, the device
performs humidifying or
dehumidifying based on
the settings.
50.0%RH
Return air sensor
The return air sensors can
be set to Enable or
Disable.
Disable
Cold aisle sensor
The sensors in cold aisles
can be set to Enable or
Disable.
Disable
Hot aisle sensor
The sensors in hot aisles
can be set to Enable or
Disable.
Disable
Settings >
System
Settings >
Indoor fan
Indoor fan control
type
R/S air temp diff rate ctrl,
R/S air temp diff ctrl, or
Pressure diff ctrl can be
set.
R/S air temp
diff rate ctrl
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
E Parameter Description
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
240