Menu
Name
Parameter Description
Default Value
Heating function
If Enable is selected, the
electric heater can be
started when the ambient
temperature is lower than
the temperature setpoint
by a certain range. If
Disable is selected, the
heating function is
disabled. If Enabled when
active power is selected,
the electric heater can be
started only when the
active power supply is used
and the ambient
temperature is lower than
the temperature setpoint
by a certain range.
Enabled when
active power
Heating mode
If Dehumidifying heating
is selected, the electric
heater determines whether
to start based on the
current temperature only
when the dehumidification
function is enabled. If Low-
temperature heating is
selected, the electric heater
is started only based on
temperature requirements,
regardless of whether the
dehumidification function
is enabled. If Dehumid &
low-temp heat is selected,
the electric heater
determines whether to
start based on the
temperature requirements
when the dehumidification
and heating conditions are
met.
Dehumid &
low-temp heat