Hot aisle
temperature and
humidity sharing
This function can be enabled only when at
least one smart cooling product in the
group is equipped with hot aisle T/H
sensors. If this function is enabled, the
master unit in the teamwork group collects
the hot aisle temperature and humidity
values from all units equipped with hot aisle
sensors, and synchronizes the temperature
and humidity values to all units after logical
calculation.
After this function is enabled, the master
unit synchronizes the temperature and
humidity control type and setpoints to all
slave units.
Motorized
damper
● Disable: The air damper function of the
unit is disabled.
● AO Ctrl: Select AO Ctrl for AO-type air
dampers.
System
Settings
Dual power
supply setting
Set this parameter as required.
● Primary power only: Select this option
when the dual-power model is connected
to the primary power only.
● Primary power first: Select this option
when the dual-power model is connected
to two power supplies.
Require password
to start or
shutdown onsite
● No: No password is required for startup
or shutdown.
● Yes: A password is required for startup
and shutdown.
Dehumidifying
function
● Enable: The device starts dehumidifying
when the ambient humidity is higher
than the humidity setpoint.
● Disable: The dehumidifying function is
disabled.
DO_1 action
This parameter can be set to On or Off, and
is used together with DO_1. For details, see
DO_1 description.
DO_2 action
This parameter can be set to On or Off, and
is used together with DO_2. For details, see
DO_2 description.
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual