6.1.2 Semi-annual Maintenance Items
Table 6-2 Semi-annual Maintenance Items
Item
Method (Monthly
Maintenance)
Troubleshooting
Monitoring
Export smart cooling
product logs and alarms
as well as the operating
status and time of the
fan, electric heater, and
wet film humidifier from
the monitoring system.
View the historical
alarms generated in this
quarter and select the
most common five ones.
(If no monitoring system
is available, skip this
item.)
Locate the cause or contact technical
support.
Electric
heater
Check that the electric
heater is fixed reliably.
Retighten the electric heater and its
switch.
Check that the electric
heater surfaces are not
eroded.
Replace the electric heater.
Wet film
humidifier
Check that the valve on
the water inlet pipe for
the wet film humidifier is
open.
When the NetCol8000-C
is on, choose Maint >
Diagnostic Mode >
Enter to start the wet
film humidifier.
If no water is supplied, check the
cable connection or replace the
water inlet solenoid valve.
Cables
Check that cables are not
aged.
Replace cables if necessary.
Differential
pressure
switch
Check that the pressure
inlet tube is not blocked
or over-bent.
Reinstall the pressure inlet tube.
Check that cables to the
differential pressure
switch are securely
connected.
Reconnect the cables.
Water
leakage
sensor
Check that the water
leakage sensor is securely
installed.
Retighten the cables.
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
6 Maintenance
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
136