Figure 6-22 Removing a wet film humidifier from an upflow unit
Step 4 Install the new wet film humidifier.
NO TICE
After replacing the wet film humidifier, properly install and secure the humidifier
water inlet pipe. Otherwise, the pipe may leak.
Step 5 Power on the device, choose Maint > Wizard Startup on the home screen, and
commission the wet film humidifier to check that it works properly before you
exit.
Step 6 On the home screen, choose Maint > Performance Maint to enter the
Performance Maint screen, and clear the runtime of the wet film humidifier.
Step 7 Choose Settings > System Settings > System Control and set Humidifying
function to Enable.
----End
6.4.6.2 Replacing a Wet Film Humidifier (for a Downflow Model)
Procedure
Step 1 Choose Settings > System Settings > System Control and set Humidifying
function to Disable.
Step 2 Open the cabinet front door.
Step 3 Remove the wet film humidifier.
1. Cut off the binding strap on the humidifier water inlet pipe and rotate the
sheet metal positioning kit.
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
6 Maintenance
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
179