Parameter
Description
Configuration Principle
Humidity
setpoint
After the temperature and
humidity control type and the
humidity value under this type
are set, the device performs
humidifying or dehumidifying
based on the settings.
Set this parameter as required.
40%–60% RH recommended
----End
4.5.2 (Optional) Setting the Pressure Difference Control
Prerequisites
If the differential pressure sensors are installed, perform the following operations
accordingly. If the differential pressure sensors are not installed, skip this part.
Procedure
Step 1 On the home screen, choose Settings > System Settings > Indoor fan, set Air-
side difference pressure sensor type to 0~500 Pa.
Step 2 Set Indoor fan control type to Pressure diff ctrl.
Step 3 Change the other parameters based on the following instructions.
Table 4-5 Parameter description
Parameter
Description
Configuration Principle
Indoor fan control type
Sets the control type for
the indoor fan.
Normally, retain R/S air
temp diff rate ctrl. If
the differential pressure
sensors are configured,
change to Pressure diff
ctrl.
Indoor fan silent mode
Set maximum speed of
indoor fan to reduce
equipment noise.
You are advised not to
change the value.
Air-side difference
pressure sensor type
Sets the measuring
range for the air side
differential pressure
sensor.
There is no default value.
Set it to 0~500 Pa.
Min indoor fan speed
Sets the minimum speed
for the indoor fan.
The default value is 60%.
You are advised not to
change the value.
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
4 Power-On Commissioning
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
102