NO TE
Historical alarms are displayed in chronological order. The latest cleared alarm is displayed
in the uppermost row.
7.4.10 How Do I Clear Component Runtime?
Context
NO TICE
Performance value clearance can only be performed after component
maintenance. Otherwise, the component may run overtime and weaken the
performance of the unit.
Procedure
Step 1 On the home screen, choose Maint > Performance Maint.
Step 2 Tap Clear in the row of a performance parameter to clear the runtime.
----End
7.4.11 How to Calibrate a Sensor
Context
Calibrate a sensor if the displayed temperature or humidity on the sensor deviates
from the actual value. For example, if the return air temperature measured by
other temperature detection devices at the return air detection point is 20°C while
the value measured by the sensor is 22°C, the sensor has an error of 2°C, and the
calibration value should be set to –2°C.
Procedure
Step 1 On the home screen, choose Maint > Sensor Calibration.
Step 2 Fill the calibration value based on the measured error.
----End
7.4.12 How Do I Change the Password?
Prerequisites
●
If you need to change a password, log in as user admin or operator.
●
You can only change the password of the current user.
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
7 FAQ
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
200