Symptom
Possible Cause
Troubleshooting
The cable to the water
inlet solenoid valve is
incorrectly connected.
Reconnect the cable.
The
humidification
capacity is
insufficient.
The wet film humidifier
wears out and
deteriorates.
Replace the wet film humidifier.
The air filter is
blocked.
The air filter has been
used for too long and
become dusty.
Replace the air filter.
The differential pressure
switch is faulty.
Replace the differential pressure
switch.
The pressure
difference cannot
be controlled.
The differential pressure
sensor is faulty.
Replace the differential pressure
sensor.
The pressure tube is
blocked or over-bent.
Replace the pressure tube or
route the pressure tube again.
The motorized
damper does not
operate.
The actuator cable is
not properly connected.
Check and reconnect the cable
to the motorized damper
actuator.
The actuator is faulty
and does not operate.
Replace the actuator.
The air damper is stuck.
Replace the air damper.
The direct free-
cooling plenum
does not operate.
The actuator cable is
not properly connected.
Check and reconnect the cable
to the air damper actuator.
The actuator is faulty
and does not operate.
Replace the actuator.
The air damper is stuck.
Replace the air damper.
The air filter of
the fresh air unit
is blocked.
The air filter has been
used for too long and
become dusty.
Clean or replace the air filter.
The differential pressure
switch is faulty.
Replace the differential pressure
switch.
6.4 Parts Replacement
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
6 Maintenance
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
162