Alarm ID
Alarm Name
Alarm
Severity
Possible Cause
Solution
A172-01
SPD and voltage
detection board comm
failed
Major
● The
communications
cable is not
connected properly.
● The SPD and
voltage detection
board is faulty.
● The
communications
port of the main
control board is
faulty.
1. Check the
communications
cable.
2. Replace the SPD
and voltage
detection board.
3. Maintain or replace
the main control
board.
A174-01
SPD function failure
Major
The SPD and voltage
detection board is
faulty.
Replace the SPD and
voltage detection
board.
A174-02
SPD function failure
Major
● The SPD is faulty.
● The cable to the
SPD is not
connected properly.
1. Replace the SPD.
2. Check the cable
connection to the
SPD.
A179-01
Humidifier function
abnormal alarm
Major
● The humidifier
pump inlet is
blocked.
● The float does not
drop because the
humidifier float is
faulty.
● The cable to the
humidifier pump is
not connected
properly.
● The humidifier
pump is faulty.
● The water pump is
blocked.
1. Clear the blockage
from the humidifier
pump inlet.
2. Maintain the
humidifier float.
3. Check the cable
connection to the
humidifier pump.
4. Replace the
humidifier pump.
5. Replace the water
pump.