Parameter
Description
Networking
mode
Specifies the networking mode for
teamwork control. The networking mode
selected on the screen must match the
actual networking mode. Otherwise, the
teamwork function is unavailable.
Number of
systems in this
group
Specifies the total number of units in this
group. The value is an integer ranging from
1 to 32.
NOTE
This parameter is displayed after Teamwork
function is set to Enable.
Number of
running systems
in this group
Specifies the number of running units in this
group. The value is an integer ranging from
1 to the value of Number of systems in
this group.
NOTE
This parameter is displayed after Teamwork
function is set to Enable.
System
Optional
Parts
Return air sensor
Enables or disables a sensor.
Cold aisle sensor
Enables or disables a sensor.
Hot aisle sensor
Enables or disables a sensor.
Cold aisle
temperature and
humidity sharing
This function can be enabled only when at
least one smart cooling product in the
group is equipped with cold aisle T/H
sensors. If this function is enabled, the
master unit in the teamwork group collects
the cold aisle temperature and humidity
values from all units equipped with cold
aisle sensors, and synchronizes the
temperature and humidity values to all
units after logical calculation.
After this function is enabled, the master
unit synchronizes the temperature and
humidity control type and setpoints to all
slave units.
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
4 Power-On Commissioning
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
93