Table 3-1 Pipe ports
Item
Specifications
Water outlet pipe
G 2 inch port with internal threads
Water inlet pipe
G 2 inch port with internal threads
Humidifier water inlet pipe
G 3/4 inch port with external threads
Drainpipe
G 3/4 inch port with internal threads
Installation Requirements
Table 3-2 Installation requirements
Item
Specifications
Door
Width ≥ 1.7 m; height ≥ 2.3 m; turning radius ≥
3.2 m
Floor
Floor bearing capacity ≥ 400 kg/m
2
Pipe routing
Upflow: left pipe routing, left and bottom pipe
routing
Downflow: left and bottom pipe routing
Maintenance distance
Front maintenance distance ≥ 900 mm
Power distribution
requirements
Leakage circuit breakers are not recommended
for the main power route. If leakage circuit
breakers are required by the customer or by
local regulations, use the residual current
circuit breaker (RCCB) that is not sensitive to
the single-phase DC pulses and transient
current pulses.
3.2 Installation Preparations
3.2.1 Tools
and
list the tools for installing the
NetCol8000-C. Add or delete tools as required.
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
3 Installation