If the information shown in
is displayed on the controller LCD,
the smart cooling product cannot run properly. Perform
and
subsequent steps.
Figure 4-50 Message 2
NO TE
In the
the ACC V100R001C20SPC300 version is used as an example to describe
the WebUI prompt messages. During actual operations, the version in use prevails.
Procedure
Step 1 Check whether strong electromagnetic interference exists around the E-label
identification board.
●
If yes, contact Huawei technical support.
●
If no, continue with
Step 2 Disconnect the power supply of the smart cooling product.
Step 3 Check whether the E-label identification board is properly connected.
●
If no, reconnect the board properly and continue with
●
If yes, continue with
Step 4 Check whether cables are properly connected.
●
If yes, contact Huawei technical support to replace the E-label identification
board.
●
If no, reconnect or replace cables and perform
.
Step 5 Reconnect the power supply of the smart cooling product.
Step 6 If the fault persists, contact Huawei technical support.
----End