Procedure
Step 1 Check whether the low-temperature component is connected.
●
If the low-temperature component is not connected, vacuumize the cooling
system from the two positions (liquid pipe needle valve and low-pressure
needle valve) at the same time, as shown in
Figure 5-2 Vacuumizing the cooling system without configuring low-temperature
component
(1) Liquid pipe needle valve
(2) Low-pressure needle valve (3) Low-pressure gauge valve
(4) Nut
(5) High-pressure gauge valve (6) Vacuum pump
●
If the low-temperature component is connected, vacuumize the cooling
system from the three positions (liquid pipe needle valve, low-pressure needle
valve, and discharge pipe needle valve) at the same time, as shown in