Al
ar
m
ID
Alar
m
Alar
m
Seve
rity
Defau
lt
Value
Impac
t
Possible Cause
Solution
a0
41
Cond
pum
p
fault
MAJ
OR
-
The
alarm
is
genera
ted.
1. The cables to the
cond pump are
loose or
damaged.
2. The cond pump
is faulty.
3. The fuse or relay
of the cond
pump is faulty.
4. The drainage
capacity of the
cond pump
decreases, or the
drainpipe is
blocked.
1. Check the
cables to the
cond pump.
2. Replace the
cond pump.
3. Replace the
fuse or relay of
the cond pump.
4. Replace the
cond pump or
remove the dirt
from the
drainpipe.
a0
42
Rem
ote
shut
down
Critic
al
N/A
The
alarm
is
genera
ted,
and
the
system
shuts
down.
1. The remote
shutdown dry
contact is
triggered.
2. The cables to the
remote
shutdown dry
contact is faulty.
1. Check the
status of the
remote
shutdown dry
contact.
2. Check the
cables to the
remote
shutdown dry
contact.
a0
43
Floor
wate
r
overf
low
Critic
al
N/A
The
alarm
is
genera
ted,
and
the
system
shuts
down.
1. Water exists on
the floor.
2. The water sensor
is faulty.
1. Check and clean
the water.
2. Maintain or
replace the
water sensor.