NO TICE
● Certain circuits in the NetCol5000-A has lethal voltage. Only professional
technicians are allowed to perform maintenance.
● Exercise caution during live-line troubleshooting.
● If jumpers are used for troubleshooting, remove them after troubleshooting.
Connected jumpers may affect control functions and damage equipment.
describes how to troubleshoot the NetCol5000-A.
Table 6-7 Troubleshooting
Symptom
Possible Cause
Solution
The unit generates
abnormal voice.
Compressor, fans, or
pipes are loose.
Check the fixing
structure and ensure that
all components are
securely installed.
A compressor does not
work.
The high-pressure switch
reacts.
Check the high-pressure
switch status.
Circuit breakers, fuses, or
cables are disconnected.
Check the main circuit
breaker, compressor
circuit breakers, fuses,
and cables.
A compressor motor is
damaged.
Replace the motor.
A compressor does not
need to start.
Check for any startup
requirement on the LCD.
The compressor exhaust
temperature is too high.
The refrigerant loop or a
component is blocked.
Check whether the
refrigerant loop or a
component is blocked.
The outdoor unit is
installed in an
inappropriate position.
(The outdoor unit should
not be exposed to direct
sunlight and must be
installed at a specified
spacing according to the
installation guide.)
Install the outdoor unit
in a correct position,
without exposure to
direct sunlight and with
an appropriate spacing.
Air exists in the cooling
system.
Exhaust air, and examine
and repair the pipeline.
Heat dissipation is poor
because of blockages in
the condenser.
Clean the condenser fins.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
6 System Operation and Maintenance
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
199