Al
ar
m
ID
Alar
m
Alar
m
Seve
rity
Defau
lt
Value
Impac
t
Possible Cause
Solution
a0
82
Powe
r
overv
olt
Majo
r
114%
The
alarm
is
genera
ted,
and
the
system
shuts
down.
1. The power
supply voltage is
higher than the
power overvolt
alarm thres.
2. The voltage
jumper
connected to the
smart cooling
product unit is
incorrect.
1. Check the
power supply
voltage.
2. Maintain or
replace the
voltage jumper.
a0
83
Surg
e
prote
ction
boar
d
fault
Majo
r
N/A
The
alarm
is
genera
ted.
1. The SPD is
faulty.
2. The cables to the
SPD are loose or
damaged.
3. The port of the
control board is
faulty.
1. Maintain or
replace the SPD.
2. Check the
cables to the
SPD.
3. Maintain or
replace the
control board.
a0
84
Powe
r
fault
Critic
al
N/A
The
alarm
is
genera
ted,
and
the
system
shuts
down.
1. No voltage
jumper is
connected to the
smart cooling
product unit.
2. The voltage
jumper is faulty.
1. Connect a
correct voltage
jumper to the
smart cooling
product unit.
2. Maintain or
replace the
voltage jumper.
a0
85
Rout
e A
fuse
disco
nnect
Critic
al
N/A
The
alarm
is
genera
ted,
and
the
system
shuts
down.
1. A device on loop
A is faulty.
2. The loop A fuse
is loose, aged, or
disconnected.
1. Maintain or
replace the
faulty device on
loop A.
2. Maintain or
replace the
fuse.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
6 System Operation and Maintenance
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
186