Figure 3-4 Pagoda connector (unit: mm)
3.1.2.5 Pipe Support
shows supports for refrigerant pipes and water pipes. The actual
appearance of the supports will be different based on onsite situations.
Figure 3-5 Pipe supports (unit: mm)
NO TE
● The height of the U-shaped pipe clamp is 5 mm less than the pipe diameter (including
the thermal insulation foam). Pipe supports are subject to engineering procurement.
● It is recommended that pipe supports and pipe clamps be made of 304 stainless steel.
● Install a support every 1500 mm for the straight sections of pipes, and 500 mm away
from each bending point in turning sections.
3.1.2.6 Cables
describes the cables to be connected onsite. Signal cables should be
routed through a protective tube.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
3 Installation Guide
Issue 17 (2020-10-22)