Table 3-10 Cable specifications
Name
Specifications
Quantity
Remarks
Indoor unit
power
cable
Four-core cable
a
: electrical power
cable-600 V/1000 V-ZA-RVV-6 mm
2
-46
A
1 PCS (The
length is
determine
d in
presale
survey.)
Optional
L1, L2, and L3 terminals: common
terminal-single cord end terminal-6
mm
2
-0.02 m-30 A-inserted depth 12
mm
6 PCS
Mandatory
PE terminals: naked crimping terminal-
OT-6 mm
2
-M6-50 A-tin plated-12 AWG
to 10 AWG
2 PCS
Mandatory
Outdoor
unit power
cable
For detail cable specifications, see the
outdoor unit user manual.
1 PCS
Optional
Voltage
jumper
Six voltage jumpers are available in the
fitting bag. Select one for use.
1 PCS
Mandatory
Outdoor
unit on/off
signal
cable
For details about the cable
specifications, see the outdoor unit user
manual.
1 PCS
Optional
Water
sensor
signal
cable
Power cable-5m-22AWG-(2 x T0.5
2
)-(2
x 22UL1007)-(2 x T0.5
2
)
1 PCS
Mandatory
Teamwork
networkin
g cable
It also can be used for host monitoring.
1 PCS
(10m)
Mandatory
Humidity
and
temperatu
re sensor
and its
cable
N/A
Max 6 PCS Optional
a: If you use a five-core cable, do not install the neutral wire (blue). Instead, cut
off it and properly wrap PVC insulation tape around the cutting place. Purchase
indoor unit power cables with qualified diameters (16.8–18 mm). Otherwise, the
power cables will fail to be routed through the clip.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
3 Installation Guide
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
34