4.7.6 How to Fast Shut Down an Smart Cooling Product
Procedure
Step 1 On the home screen of the ACC, tap Shutdown.
The compressor stops running and the fan is shut down after the time delay.
Step 2 Disconnect the power supply from the smart cooling product.
NO TE
If the power supply is disconnected when the device is on, the following situation may
occur after the device is powered on again:
● A power loss alarm is displayed on the ACC and automatically cleared in 10s.
● The system retains the Start status before the power disconnection.
----End
4.7.7 How to Manually Clear Alarms
Context
●
This topic uses the Comp HP switch lock alarm as an example to describe how
to manually clear alarms.
●
If you need to manually clear alarms, log in as the Admin or Engineer user.
Procedure
Step 1 Tap Alarms > Query Act. Alarms > Comp HP lock on the home screen. The
alarm information is displayed, as shown in
.
Figure 4-43 Manually clearing the alarm
Step 2 Tap Clear, a dialog box for confirming clearance is displayed.
Step 3 Tap Yes, the Command triggered successfully. message is displayed.
Step 4 Tap OK.
----End
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
4 ACC Introduction