CA UTION
Before connecting signal cables to an outdoor unit, take effective ESD protection
measures.
Ports
shows the zoomed-in view of the control terminal XT2 ports,
including ports for reporting common alarms 1 and 2, port for the outdoor unit
on/off signal cable, port for the remote shutdown of an indoor unit, water sensor
port, smoke sensor port, and port for reporting mains outage alarm.
Figure 3-41 Zoomed-in view of the control terminal XT2 ports
NO TE
For the actual terminal layout, refer to the site layout. This figure is for reference only.
describes the definitions and functions of control ports.
Table 3-15 Definitions and functions of control ports
Port
Nam
e
Definition
Function
Port Feature
X2.1,
X2.2
Port for
reporting
common
alarm 1
Alarm dry contact output.
When DO associated
alarm is set to Critical
ALM, the smart cooling
product issues an alarm if a
major alarm occurs.
NO signal dry contact
output. Connection to an
outdoor device is
forbidden.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
3 Installation Guide
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.