dropping, pump for another 10 minutes. The indication of sight glass is dry
(green).
Step 5 Close all the pressure gauge valves, and the vacuum pump after vacuumizing the
cooling system. Preserve the pressure for 10 minutes without disconnecting the
connection. The pressure should be lower than and equal to 90 Pa (absolute
pressure).
NO TE
If the precision of the pressure gauge is too low to display 60 Pa (absolute pressure), ensure
that the pressure gauge pointer stayed at the minimum scale while vacuumizing the
cooling system, preserve the pressure for 1 hour, and check whether the displayed pressure
increases obviously.
----End
5.2.4 Partially Charging Refrigerant
Prerequisites
NO TICE
● Charge refrigerant (R410A) right after checking that the cooling system does
not leak and the vacuum level meets the requirements.
● Calculate the refrigerant amount to be charged by referring to
Calculation about the Charged the Refrigerant and Refrigerant Oil
● Before charging refrigerant, ensure that the air is exhausted from the hose
connecting to the refrigerant steel vessel.
Procedure
Step 1 Take off the vacuum pump from the vacuumizing equipment, and replace the
vacuum pump with a refrigerant steel vessel.
Step 2 Partially open the refrigerant steel vessel valve and rubber tube nut shown in
. Tighten the nut when you feel cold air coming out from the nut.
Step 3 Put the refrigerant steel vessel upside down on an electric balance. Clear the
reading on the balance.
NO TICE
If the R410A refrigerant is provided by Huawei, put the refrigerant steel vessel
upside down when charging in the refrigerant. If the refrigerant is not provided by
Huawei, check with the refrigerant provider whether the steel vessel has a siphon.
If the vessel has a siphon, put it upside up when charging in refrigerant. If the
vessel has no siphon, put it upside down when charging in refrigerant. These
measures ensure that the refrigerant is charged in the liquid form.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)