Figure 5-4 Breakers
(1) Compressor circuit breaker
QF3
(2) Electric heater circuit
breaker QF4
(3) Humidifier circuit breaker
QF5
(4) General circuit breaker QF1 (5) Fan circuit breaker QF6
(6) Main control board power
circuit breaker QF8
(7) Condensate pump circuit
breaker QF9
5.3.3 Power-On
Context
All circuit breakers are set to OFF before delivery. If the preset status has been
changed, restore the preset status before any operation.
Procedure
Step 1 Subsequently switch on main control board power circuit breaker QF8 and general
circuit breaker QF1.
NO TE
Alarms and LCD buzzer noise may occur if the compressor and fan circuit breakers are not
switched on. The alarms and buzzer noise disappear when the switches are closed.
Step 2 Measure the controller loop voltage by using a voltmeter, as shown in
.
Ensure that the control voltage is within the range of 24 V AC (tolerance ±10%). If
the voltage is not within the range, check whether the voltage jumper matches
the mains, or whether the current input voltage meets normal voltage
requirements.