a0
68
Com
p
drive
overc
urren
t
Majo
r
N/A
The
alarm
is
genera
ted.
1. The comp is in
lack of oil.
2. The condenser
fins are blocked.
3. The outdoor
units do not run
properly.
4. The solenoid
valve is faulty.
5. The refrigerant is
overfilled.
6. The comp is
faulty.
1. Fill oil to the
comp.
2. Clean the
condenser fins.
3. Maintain or
replace the
outdoor units.
4. Maintain or
replace the
solenoid coil or
the solenoid
valve.
5. Decrease
certain amount
of refrigerant.
6. Maintain or
replace the
comp.
a0
69
Com
p
start
faile
d
Majo
r
N/A
The
alarm
is
genera
ted.
1. The comp is in
lack of oil.
2. The comp driver
is faulty.
3. The comp is
faulty.
1. Fill oil to the
comp.
2. Maintain or
replace the
comp driver.
3. Maintain or
replace the
comp.
a0
70
Com
p
drive
fan
fault
Majo
r
N/A
The
alarm
is
genera
ted.
The fans in the
comp driver are
faulty.
Check the fans in
the comp driver.
a0
71
Com
p
drive
mod
ule
over
heat
Majo
r
N/A
The
alarm
is
genera
ted.
1. The fans in the
comp driver are
faulty.
2. Dirt exists in the
air vents of the
fans in the comp
driver.
1. Check the fans
in the comp
driver.
2. Clean the air
vents of the
fans in the
comp driver.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
6 System Operation and Maintenance
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
181