FULLTEST3
EN - 90
RCD TEST (RCD)
RCD types / characteristics:
AC, A or B / General, Selective or Delayed
Measurement modes:
½ I
'
N, I
'
N, 2I
'
N, KI
'
N (K = 4 B type, K=5 AC, A type)
I
'
(RAMP), AUTO (sequence: x½ , x1, xK)
Nominal currents:
10, 30, 100, 300, 500, 650 or 1000 Ma
Delayed time range:
0ms ÷ 700ms adjustable
Accuracy of test currents (10 mA):
-10% / + 0% (I
'
N/2), +10% / - 0% (I
'
N, 2I
'
N, KI
'
N)
Accuracy of test currents (30
y
1000 mA):
-5% / + 0% (I
'
N/2), + 5% / - 0% (I
'
N, 2I
'
N, KI
'
N)
Input voltage range / frequency:
100 V
y
265V / (50/60Hz) ± 0.5Hz
Contact voltage limits:
25 V or 50 V selectable
Test current polarity:
0° (Positive) o 180° (Negative)
Test duration [ms] – TT/TN system
I
'
N
[mA]
×½
×1
×2
×K
AUTO
RAMP
G, S, D
G, S, D
G
S
D
G
S
D G
S
D
G
S
D
10
30
100
AC 1000 1000 200
250
X
50 150
X
X
320
X
X
A 1000 1000 200
250
X
50 150
X
X
320
X
X
B 1000 1000
X
X
X
200 250
X
X
320
X
X
300
AC 1000 1000 200
250
X
50 150
X
X
320
X
X
A 1000 1000 200
250
X
50 150
X
X
320
X
X
B 1000 1000
X
X
X
X
X
X
X
X
X
320
X
X
500
AC 1000 1000 200
250
X
50 150
X
X
320
X
X
A 1000 1000 200
250
X
X
X
X
X
X
X
320
X
X
B 1000 1000
X
X
X
X
X
X
X
X
X
320
X
X
650
AC 1000 1000 200
250
X
50 150
X
X
320
X
X
A 1000 1000 200
250
X
X
X
X
X
X
X
320
X
X
B
X
X
X
X
X
X
X
X
X
X
X
X
X
X
1000
AC 1000 1000 200
250
X
X
X
X
X
X
X
320
X
X
A 1000 1000
X
X
X
X
X
X
X
X
X
X
X
X
B
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Resolution: 1ms, Accuracy: ± 3%rdg + 2ms)
X = test not possible
Mains voltage UL/N, UL/PE
Range
[V]
Resolution
[V]
Accuracy
100
y
265
1 ±
(3%rdg)
Input resistance (UL/N, UL/PE):
450 k
:
Ramp test:
current range 10%
y
110% of I
'
N in steps of 5% of I
'
N
AUTO TEST:
test steps are as follows: t/I
'
N/2 (0°), t/I
'
N/2 (180°), t/I
'
N (0°),
t/I
'
N (180°), t/5I
'
N (0°), t/5I
'
N (180°)