6. OPERATIVE INSTRUCTIONS
6.1. CONTINUITY OF PE CONDUCTOR – 2-WIRE METHOD (R
PE-2WIRE
)
Complying with IEC/EN60204-1 the continuity of protective bonding circuit between
PE terminal and relevant points of the protective conductor system must be checked
by injecting a measurement current of 0.2 A up to 10 A approx. The instrument allows
to perform the test with 200mA and 25A test current (for resistance between
terminals <0.1
:
) or 10A (for resistance between terminals <0.5
:
) with automatic
recognition.
1. Press the
FUNC
key and select the
RPE-2WIRE
function. The following screen is
shown on the display
Fig. 25 : RPE-2WIRE initial screen
2. Select the test parameters on the instrument (see Table 1) and carry out the
desired setup
Parameter Description
Value
Im NOM
Nominal test current
200mA or 25A AC (R<0.1
:
)
200mA or 10A AC (R<0.5
:
)
LIMIT
Reference limit threshold
STANDARD
0.01
:
÷ 200.0
:
(200mA)
0.01
:
÷ 20.0
:
(25A)
60204 SET L (25A)
60204 SET Z (25A)
60204 SET L
Test with 25A current
(see § 6.1.2)
Length: 0.1m ÷ 999.9m
Section: 1, 1.5, 2.5, 4, 6, 10, 16,
25, 35, 50, 70,
95, 120,
150, 185,
240,
300, 400, 500, 630
mm
2
Material: Cu (Copper) or Al
(Aluminum)
60204 SET Z
ZLine: 0.001
:
y
2.000
:
MCB protection: B, C, D, K
Fuse protection: gG, aM
Nominal current protection
(see §)
MODE Measurement
mode
Manual
Timer (2s ÷ 60min)
CAL
Test leads calibration
up to 5.00
:
Table 1 : Setup parameters of RPE-2WIRE function