Ground Bonding kit 51
4.
Insert a T-25 Torx screw through the other end of the same grounding strap, and insert it in the hole on
the rack front door. Tighten the screw.
From the system chassis rail to the front door (with a grounding lug):
1.
Insert a T-25 Torx screw through one end of a 36.83-cm (14.5-in) grounding strap, and secure it to the
system chassis rail.
2.
Place the other end of the same grounding strap over the grounding lug on the front door.
3.
Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the front door
and tighten.
From the system chassis rail to the right rear door:
1.
Insert a T-25 Torx screw through the end of a 36.83-cm (14.5-in) grounding strap, and secure it to the
system chassis rail.
2.
Place the other end of the same grounding strap over the grounding lug on the right rear door.