Ground Bonding kit 63
4.
Reinsert and tighten the front door panel screw.
From the system chassis rail to the right rear door:
1.
Insert a T-25 Torx screw through the end of a 36.83-cm (14.5-in) grounding strap, and secure it to the
system chassis rail.
2.
Place the other end of the same grounding strap over the grounding lug on the right rear door.
3.
Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the right rear
door and tighten.
From the system chassis rail to the left rear door:
1.
Insert a T-25 Torx screw through the end of a 36.83-cm (14.5-in) grounding strap, and secure it to the
system chassis rail.
2.
Place the other end of the same grounding strap over the grounding lug on the left rear door.