Heavy Duty Stabilizer kit 71
2.
Slide the rack into its final location.
3.
Raise the rack by lowering the leveling feet, raising the casters approximately 6.4 mm (0.25 in) off the
floor.
4.
Install one stabilizer foot on each side of the front stabilizer mount (1) by inserting and partially
tightening one M8 x 30-mm bolt and washer on each foot (2).
5.
Fully seat each stabilizer foot to the front stabilizer mount, and tighten the bolts from step 4.
6.
Lower the rack so that the full weight of the rack rests on the rear leveling feet and the front stabilizer
feet.
WARNING:
To reduce the risk of personal injury or damage to the equipment, be sure that:
•
The rear leveling feet are extended to the floor.
•
The full weight of the rack rests on the rear leveling feet and front stabilizer feet.
Installation is complete.