Rack Air Duct kit 103
b.
Using an electric drill, drill one 2.38-mm (3/32-in) hole through the lower duct, in the location you
marked.
c.
Insert one M3.5 self-drilling screw through the holes in both the upper and lower ducts (2).
Baying options
You can order the HP Baying Rack Option Kit to bay your HP 10000 G2 Rack Air Duct rack to another HP
10000 G2 Rack Air Duct rack. You cannot bay an HP 10000 G2 Rack Air Duct rack to a standard rack.
You must install the included gaskets to your HP 10000 G2 Rack Air Duct rack prior to baying, to ensure that
the air continues to be channeled up the air duct and not out the sides of the bayed rack.
To install the gasket strips to your rack:
1.
Remove the liner backing from each of the four gasket strips.
2.
Attach the two 876-mm gasket strips to the top and bottom frames of the side of the rack.
3.
Attach the two 1875-mm gasket strips to the front and rear frames of the side of the rack.
Summary of Contents for HP 10000 G2 Series
Page 35: ...Cable Management Bracket kit 35 Installation is complete ...
Page 74: ...Hook and Loop Cabling Strap Clip kit 74 ...
Page 75: ...Hook and Loop Cabling Strap Clip kit 75 Installation is complete ...
Page 104: ...Rack Air Duct kit 104 For more information see Baying kit on page 25 ...
Page 125: ...Vertical PDU Mounting kit 125 HP monitored PDU 2 Install the PDU The installation is complete ...