Ground Bonding kit 49
Ground Bonding kit
About this device
The HP Ground Bonding kit reduces the electromagnetic emissions outside the rack. These emissions are
produced during normal operation of the electronic components within the rack. Typically, rack-mounted
equipment must meet class A emissions levels, but you might want to reduce these levels even further. Use this
kit to tie all the conductive structural components together with conductive cables, and then attach the kit to
a ground bonding point on the AC power distribution device of the rack or the building ground.
Kit contents
Item
Quantity
15.24-cm (6-in) grounding straps
6
15.24-cm (6-in) grounding straps
(with a connector on one end)
6
36.83-cm (14.5-in) grounding straps 8
36.83-cm (14.5-in) grounding straps
(with a connector on one end)
6
M8 internal serrated lock washer
20
M8 hex nut
20
M5.5 T-25 Torx screw
12
M6 x 10-mm Torx screw
1
M8 x 20-mm bolt
1
M8 Belleville toothed washer
1
M5 Belleville toothed washer
1
This kit might contain extra hardware for your convenience.
Required tools
The following tools are required for installation:
•
T-25 Torx driver
•
M8 socket
Installing the ground bonding rack option kit on HP
10000 G2 Series Racks
Attach the appropriate grounding straps to the following locations:
From the system chassis to the front door (without a grounding lug):
1.
Remove the rack front door.
Summary of Contents for HP 10000 G2 Series
Page 35: ...Cable Management Bracket kit 35 Installation is complete ...
Page 74: ...Hook and Loop Cabling Strap Clip kit 74 ...
Page 75: ...Hook and Loop Cabling Strap Clip kit 75 Installation is complete ...
Page 104: ...Rack Air Duct kit 104 For more information see Baying kit on page 25 ...
Page 125: ...Vertical PDU Mounting kit 125 HP monitored PDU 2 Install the PDU The installation is complete ...