Installing the Control
3-19
Installing FSA ModulesThe 8-zone LED Fire System Annunciator FSA-8 and 24-zone LED Fire System Annunciator
FSA-24 enable a fire response unit to identify quickly the point/zone of a fire. These indicators may be used for other
functions as well, such as status indication. A maximum of four FSA modules, in any combination, can be supported.
The FSA module will not operate until the device address you have set the DIP switches for is enabled in the
control’s
Device Programming in the #93 Menu Mode.
To install the FSA module, refer to
Figure 3-22
and perform the following steps:
Step Action
1
Set the FSA’s DIP switches for a device address from 08 to 23. See the module’s instructions for the DIP
switch table.
Do not use an address being used by another device (keypads, RF receivers, etc.).
2
Mount the FSA module horizontally to a duplex box (quad box for FSA-24).
3
Connect the module to the control’s keypad terminals (6, 7, 8, and 9).
0 0 0 0 0
ECP Bus
Dip Switch
Optional
Keyswitch
Connection
SIDE
VIEW
All Switches shown
in Up position.
(ECP Address 23)
Terminal
Block
Connect to
Keypad
Terminals
Figure 3-22: Wiring the FSA Module
Installing 4101SN Relay Modules
The 4101SN V-Plex Single Output Relay Module is a serial number polling loop output device. The 4101SN features the
following:
•
Form C relay contacts rated at 2A, 28VAC/VDC with contact supervision.
The position of the relay is supervised, but not the actual external contact wiring.
•
One class B/style B EOLR-supervised auxiliary input zone.
•
Operating power and communication with control panels via the V-Plex polling loop.
•
Electronics mounted in a small plastic case with tamper-protected cover.
Connect the device to the polling loop, terminals 24 (+) and 25 (-). Be sure to observe polarity
Installing X10 Devices
X-10 devices are either plugged into standard AC outlets or wired into the AC
electrical system by a licensed electrician, depending on the type of device used.
Note each device’s House and Unit Code setup, as these codes will be used to program the devices in
Output
Programming in #93 Menu Mode described in the Programming Guide.
X-10 devices require the use of a 1361X10 transformer in place of the regular 1361 transformer.
X-10 devices respond to “on” and “off” commands sent from the panel through the 1361X10 transformer.
To connect the 1361X10 transformer, see
Connecting the Transformer,
later in this section.
Installing the Ground Start Module
UL
The Ground Start Module is not intended for use in UL Listed applications.
Output 1 may be used to trigger an optional Ground Start Module for installations having telephone lines that require
ground start instead of loop start operation to obtain a dial tone from the telco central office.
Summary of Contents for VISTA-128BPEN
Page 2: ......
Page 10: ......
Page 58: ...Vista 128BPEN Installation and Setup Guide 3 38 ...
Page 82: ...Vista 128BPEN Installation and Setup Guide 5 14 ...
Page 102: ...Vista 128BPEN Installation and Setup Guide 8 2 ...
Page 118: ...Vista 128BPEN Installation and Setup Guide C 2 ...
Page 126: ......