Vista-128BPEN Installation and Setup Guide
3-12
IMPORTANT NOTE:
If the installation needs to exceed or deviate from these parameters, refer to the application note on
the Honeywell website for additional polling loop wiring configurations. To access the application note:
1.
Go to the honeywell.com/security website
2.
Click the Honeywell Security & Custom Electronics link.
3.
Click the Commercial link.
4.
Click the Documentation link.
5.
Click the V-Plex Application Note.
To install polling loop devices, perform the following steps:
Step Action
1
Select devices from the list of compatible devices shown previously.
2
Set the DIP switches in the device (if required). Refer to the device’s instructions.
3
Mount each device in the desired location. Refer to the device’s instructions.
Run wires from the control panel to each device on the polling loop (see
Figure 3-15
).
4
5
Wire each device to the polling loop, making sure of the correct polarity (refer to the device’s instructions).
NOTE:
If you are using serial number devices, and intend to enroll each device through the keypad
automatically,
wire no more than 25 of these devices to the control at a time.
Then power up and
program them before connecting the next 25. Leave previously enrolled devices connected.
If you intend to
manually enter the serial numbers
via the keypad or the Compass downloading software,
all the devices may be connected before powering up to program.
POLLING LOOP RATING:
128mA MAXIMUM
5192SD
SMOKE
4190
RPM
4278
PIR
23
21
22
+
-
POLLING LOOP
25
24
TO RIGHT LOOP
poll_loop-001-V1
Figure 3-16: Polling Loop Connections to the VISTA-128BPEN
Polling Loop Supervision
A short on the polling loop is indicated by a trouble on zone 997 and reports as a trouble condition only. If annunciation
is desired, program the zone as type 05.
If a device on the polling loop fails (the panel cannot "see" that device), the system displays a trouble condition for all
zones on that device. If the panel is armed when a device fails, and the zone is a burglary zone, the will go into alarm
A trouble on zone 997 prevents a partition from being armed, unless all polling loop zones on that partition are
bypassed.
Using the 4297 Polling Loop Extender
The 4297 Polling Loop Extender may be used to provide additional polling loop current, to extend the polling loop wire
run length, and/or to provide individual electrically isolated polling loops. Refer to
Figures 3-16 and 3-17
, to follow.
DO NOT
use the 4197 Polling Loop Extender module with the VISTA-128BPEN
.
Summary of Contents for VISTA-128BPEN
Page 2: ......
Page 10: ......
Page 58: ...Vista 128BPEN Installation and Setup Guide 3 38 ...
Page 82: ...Vista 128BPEN Installation and Setup Guide 5 14 ...
Page 102: ...Vista 128BPEN Installation and Setup Guide 8 2 ...
Page 118: ...Vista 128BPEN Installation and Setup Guide C 2 ...
Page 126: ......