SIA CP-01 Quick Reference Chart
The minimum required system for SIA CP-01 is a UL Listed Control, Keypad and Bell.
Item Feature
Range
Shipping
Default
SIA
Requirement*
*09
Entry Delay # 1
02 – 15 multiplied by 15
seconds
00 = 240 sec (4
minutes)
30 Seconds`
At least 30 Seconds **
*10 Exit
Delay
#1
03
– 15 multiplied by 15
seconds
60 Seconds
60 Seconds
*11
Entry Delay # 2
02 – 15 multiplied by 15
seconds
00 = 240 sec (4
minutes)
30 Seconds
At least 30 Seconds **
*12 Exit
Delay
#2
03
– 15 multiplied by 15
seconds
60 Seconds
60 Seconds
*28
Power Up in Previous
State
0 = no
1 = yes
Yes Yes
*57 Dynamic
Signaling
Priority
0 = primary dialer
1 = Communicator as
first reporting
destination
0 (primary dialer)
0 (primary dialer)
*84 Swinger
Suppression
01= 1 alarm
02= 2 alarms
1 alarm
1 alarm
*88 Abort
Window
Time
(for non-fire zones)
1 = 15 seconds
2 = 30 seconds
3 = 45 seconds
30 Seconds
At least 15 Seconds **
1*21
Exit Time Reset
0=no
1=Resets Exit Delay to
programmed value after
zone is closed and then
faulted prior to end of
exit delay.
1 (Enabled)
1 (Enabled)
1*22 – 1*25
Cross Zoning
Zone 001 – 128
000, 000 = Disabled
Disabled
Enabled and two (or
more) zones
programmed
1*42
Call Waiting Defeat
0 = no
1 = yes
Disabled (0)
Enabled if user has
call waiting
1*61
Abort Verify
0 = Disable
1 = Enable
Enabled Enabled
Zone
Programming
Auto Stay
Zone, Zone
type 04 has
this feature
enabled by
default
Auto Stay Arm or
Occupied Premises
0 = Disable
1 = Enable
1 (Enabled)
Enabled
Summary of Contents for VISTA-128BPEN
Page 2: ......
Page 10: ......
Page 58: ...Vista 128BPEN Installation and Setup Guide 3 38 ...
Page 82: ...Vista 128BPEN Installation and Setup Guide 5 14 ...
Page 102: ...Vista 128BPEN Installation and Setup Guide 8 2 ...
Page 118: ...Vista 128BPEN Installation and Setup Guide C 2 ...
Page 126: ......