Use Table 5 to determine the required backup battery capacity and use Table 6 to determine the battery model number.
A dual battery harness is supplied
that allows two batteries to be wired in parallel for increased capacity.
5.
Using the total calculated from Table 4, calculate the battery capacity required for the installation.
Table 5: Battery Capacity Calculation Table
Capacity
Formula
Calculated
Value
Standby
Capacity
For 4-hour standby time:
Total
standby current
X 4 hours X
1.4 contingency factor.
For 24-hour standby time:
Total
standby current
X 24 hours
X 1.1 contingency factor.
Alarm
Capacity
For 4-, 5-, or 15-minute alarm time:
Total
alarm curr.
X 0.067 (4 min)
0.250
(15
min)
Total
Capacity
Add standby and alarm
capacities
6.
Use the Battery Selection Table to select the appropriate battery for the installation.
Table 6: Battery Selection Table
Capacity Recommended
Battery Comment
4AH Yuasa
NP4-12
7AH Yuasa
NP7-12
12AH
Yuasa NP12-12
Fits in large
mercantile
cabinet only.
14AH
Yuasa NP7-12
Connect two
in parallel.
17.2AH
Yuasa NPG18-12
Fits in large
mercantile
cabinet only.
The standby battery is automatically tested
for 10 minutes every 4 hours, beginning 4
hours after exiting Programming mode. In
addition, entry into the Test mode initiates
a battery test. The VISTA-128BPEN also
runs a 5-second battery test every 60
seconds to check if the battery is
connected.
Summary of Contents for VISTA-128BPEN
Page 2: ......
Page 10: ......
Page 58: ...Vista 128BPEN Installation and Setup Guide 3 38 ...
Page 82: ...Vista 128BPEN Installation and Setup Guide 5 14 ...
Page 102: ...Vista 128BPEN Installation and Setup Guide 8 2 ...
Page 118: ...Vista 128BPEN Installation and Setup Guide C 2 ...
Page 126: ......