Vista-128BPEN Installation and Setup Guide
2-6
Multi-Panel View Mode
To perform a function in the Multi-Panel View mode, follow the steps below:
Step Action
1
Enter
User Code (for users 001-050)
+
[#]
+
[87].
The keypad displays the following typical display:
ALLPANEL 1 2 3 4 5 6 7 8
STATUS
x x x x x x x x
where “12345678” are the panel ID numbers and “xxxxxxxx” is the overall status of each panel. Status
indications include:
A
= Armed Away
S
= Armed Stay
M
= Armed Maximum
I
= Armed Instant
R
= Ready
N
= Not Ready
B
= Bypassed/Ready
✴
= Alarm
T
= Trouble
F
= Fire Alarm
P
= AC Power Failure
L
= Low System Battery
C
= Comm Fail
NOTE:
See table later in this section for priority of displays.
2
The following functions can be performed::
Press
[1]
to attempt to disarm all partitions on all panels.
Press
[2]
to attempt to arm AWAY all partitions on all panels.
Press
[3]
to attempt to arm STAY all partitions on all panels.
Press
[4]
to attempt to arm MAXIMUM all partitions.
Press
[7]
to attempt to arm INSTANT all partitions.
Press
[0]
to exit mode. After a few seconds, the keypad displays the status of the original partition of the
original panel for the keypad. Also, this mode will end in approximately 2 minutes if no keys are pressed.
NOTES:
When performing any of the arming commands, if there are faults in any of the partitions of a panel, the
system will not arm that panel, but will arm all the other partitions of the other panels.
When performing either a STAY or INSTANT arm command, the system always arms in mode 1 (see the
VISTA-128BPEN User Guide
for a detailed explanation of the STAY and INSTANT arming modes).
The user cannot execute another panel linking mode. In order to perform another panel linking mode or to
access a different remote panel, the user must first exit this mode (return to the original control panel).
Priority of Displays for Multi-Partition and Multi-Panel Modes
This table shows the priority of displays if more than one of these conditions exists at the same time.
Priority Description Display
Priority Description Display
1 Fire
Alarm
F
8 Not
Ready
N
2
All Other Alarms
✴
9 Ready
R
3 AC
Loss
P
10 Armed
STAY
S
4 Comm
Fail
C
11 Armed
AWAY
A
5
System Low Battery
L
12 Armed
INSTANT
I
6 Trouble
T
13 Armed
MAXIMUM
M
7 Bypass
B
Summary of Contents for VISTA-128BPEN
Page 2: ......
Page 10: ......
Page 58: ...Vista 128BPEN Installation and Setup Guide 3 38 ...
Page 82: ...Vista 128BPEN Installation and Setup Guide 5 14 ...
Page 102: ...Vista 128BPEN Installation and Setup Guide 8 2 ...
Page 118: ...Vista 128BPEN Installation and Setup Guide C 2 ...
Page 126: ......