Section 5 – Data Field Descriptions
5-9
FIELD
TITLE and DATA ENTRIES
EXPLANATION
1*22
Cross Zoning Pair One
Enter
001-128
Enter
000,000
to disable
Select the first pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm.
Must be 000,000 for UL installations.
1*23
Cross Zoning Pair Two
Enter
001-128
Enter
000,000
to disable
Select the second pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm.
Must be 000,000 for UL installations.
1*24
Cross Zoning Pair Three
Enter
001-128
Enter
000,000
to disable
Select the third pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm.
Must be 000,000 for UL installations.
1*25
Cross Zoning Pair Four
Enter
001-128
Enter
000,000
to disable
Select the fourth pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm.
Must be 000,000 for UL installations.
1*26
Panic Button or Speedkey
For A, B, C keys:
00
= panic function
01-32
= macro number
For D key:
00
= to select a macro to execute when key
is pressed
01-32
= macro number
Select for the A, B, and C keys whether the system performs a panic or a
speedkey function when the key is pressed.
Select for the D key whether the system performs a specific macro or if the
user will select a macro when the key is pressed.
NOTES:
If using the A, B, and C, keys for panic alarms, verify fields *22 and *85 are
programmed correctly.
If a user code with global arm/disarm is used to execute the macro, the user’s
global capabilities will override any arm/disarm commands in the macro
sequence.
1*28
RF Transmitter Low Battery
Sound
0
= disarmed state only
1
= both armed and disarmed states
Select when the RF transmitter low-battery condition should display and
audible beep annunciate on the keypad.
Must be
1
for UL installations.
1*29
RF Transmitter Low Battery
Reporting
0
= disable
1
= enable
If enabled, the system sends a Trouble message for RF transmitter low-
battery condition to the central station.
NOTE:
The Trouble message will be sent for a transmitter supervision failure,
independent of this selection.
Must be
1
for UL.
1*30
RF Receiver Supervision Check-
in Interval
Enter
02-15
times 2 hours (4-30 hours).
00
= disable receiver supervision.
Select the check-in monitoring interval for the RF receiver(s).
Failure of a receiver to receive any RF signal within the time entered results in
the activation of the response type programmed for zone 990 for the first
receiver and zone 988 for the second receiver and their related
communication reports.
Maximum is 2 (4 hr) for UL installations.
1*31
RF Transmitter Check-in Interval
Enter
02-15
times 2 hours (4-30 hours).
00
= disable transmitter supervision.
Select the check-in monitoring interval for the RF transmitters.
Failure of an individual transmitter to send a supervision signal within the time
entered will result in a trouble response and related communication report.
Maximum is 2 (4 hr) for UL.
1*33
TouchTone with Rotary Backup
0
= disable
1
= enable
If enabled, the system reverts to rotary dialing if communicator is not
successful in dialing using TouchTone DTMF on first attempt.
1*34
Communicator Split Reporting
0
= Split Reporting disabled
1
= Alarm, Alarm Restore, and Cancel
reports to primary, all others to secondary
2
= Open/Close and Test reports to
secondary, all other reports to primary
Select the type of split reporting for system communication.
NOTE:
See *51 for split/dual reporting combinations.
NOTE:
Split reporting should not be used with Dynamic Signaling.
Summary of Contents for VISTA-128BPEN
Page 2: ......
Page 10: ......
Page 58: ...Vista 128BPEN Installation and Setup Guide 3 38 ...
Page 82: ...Vista 128BPEN Installation and Setup Guide 5 14 ...
Page 102: ...Vista 128BPEN Installation and Setup Guide 8 2 ...
Page 118: ...Vista 128BPEN Installation and Setup Guide C 2 ...
Page 126: ......