HVAC A
PPLICATION
Honeywell
• 42
3.5.7.2
Analog inputs
Code
Parameter
Min
Max
Unit
Default
ID
Description
M3.5.2.1
AI1 signal selection
AnIN
SlotA.1
377
Connect the AI1 signal to the
analog input of your choice
with this parameter.
Programmable.
M3.5.2.2
AI1 signal filter time
0.00
300.00
s
0.1
378 Filter time for analog input
M3.5.2.3
AI1 signal range
0
1
0
379
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
M3.5.2.4
AI1 custom. min
-160.00
160.00
%
0.00
380
Custom range min setting
20% = 4-20 mA/2-10 V
M3.5.2.5
AI1 custom. max
-160.00
160.00
%
100.00
381 Custom range max setting
M3.5.2.6
AI1 signal inversion
0
1
0
387
0 = Normal
1 = Signal inverted
M3.5.2.7
AI2 signal selection
AnIN
SlotA.2
388 See M3.5.2.1.
M3.5.2.8
AI2 signal filter time
0.00
300.00
s
0.1
389 See M3.5.2.2.
M3.5.2.9
AI2 signal range
0
1
1
390
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
M3.5.2.10
AI2 custom. min
-160.00
160.00
%
0.00
391 See M3.5.2.4.
M3.5.2.11
AI2 custom. max
-160.00
160.00
%
100.00
392 See M3.5.2.5.
M3.5.2.12
AI2 signal inversion
0
1
0
398 See M3.5.2.6.
M3.5.2.13
AI3 signal selection
AnIN
Slot0.1
141
Connect the AI3 signal to the
analog input of your choice
with this parameter.
Programmable.
M3.5.2.14
AI3 signal filter time
0.00
300.00
s
0.1
142 Filter time for analog input
M3.5.2.15
AI3 signal range
0
1
0
143
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
M3.5.2.16
AI3 custom. min
-160.00
160.00
%
0.00
144 20% = 4-20 mA/2-10 V
M3.5.2.17
AI3 custom. max
-160.00
160.00
%
100.00
145 Custom range max setting
M3.5.2.18
AI3 signal inversion
0
1
0
151
0 = Normal
1 = Signal inverted
M3.5.2.19
AI4 signal selection
AnIN
Slot0.1
152
See M3.5.2.13. Programma-
ble.
M3.5.2.20
AI4 signal filter time
0.00
300.00
s
0.1
153 See M3.5.2.14.
M3.5.2.21
AI4 signal range
0
1
0
154
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
M3.5.2.22
AI4 custom. min
-160.00
160.00
%
0.00
155 See M3.5.2.16.
M3.5.2.23
AI4 custom. max
-160.00
160.00
%
100.00
156 See M3.5.2.17.
M3.5.2.24
AI4 signal inversion
0
1
0
162 See M3.5.2.18.
M3.5.2.25
AI5 signal selection
AnIN
Slot0.1
188
Connect the AI5 signal to the
analog input of your choice
with this parameter.
Programmable.
M3.5.2.26
AI5 signal filter time
0.00
300.00
s
0.1
189 Filter time for analog input
M3.5.2.27
AI5 signal range
0
1
0
190
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
M3.5.2.28
AI5 custom. min
-160.00
160.00
%
0.00
191 20% = 4-20 mA/2-10 V
M3.5.2.29
AI5 custom. max
-160.00
160.00
%
100.00
192 Custom range max setting