Honeywell
• 35
P
OWER
CABLING
Figure 34.
8
If you use thick cables insert the cable separators in between the terminals in
order to avoid contact between the cables.
9
Connect the cables stripped as shown in Figure 27.
•
Connect the (phase) conductors of the supply, brake and motor cables
into their respective terminals (a).
•
Form the rest of the cable shield of all cables into “pigtails” and make a
grounding connection as shown in Figure 35 (b) using the clamp from the
Accessories bag
.
•
Note also correct position of the ferrite holder (c) AFTER the cable strip-
ping (in MR8 and EMC class C2 only).
•
Note: If you use several cables on one connector observe the position of
cable lugs on top of each other. See Figure 36 below.