The PID controller output is locked if the actual value stays within the deadband area around
the reference for a predefined time. This function will prevent unnecessary movement and wear
on actuators, e.g. valves.
Figure 17. Dead band
100K18.fh11
Dead band (M3.12.1.9)
Reference
Dead band delay (M3.12.1.10)
Output locked
Actual value