HVAC A
PPLICATION
Table 54. Output signals via RO1
M3.7.8
R
ESONANCE
SWEEP
ACC
/
DEC
TIME
The anti-resonance function slowly sweeps through frequencies from MinFreq to MaxFreq and
back to MinFreq with the ramp times set with this parameter. During this sweep, the user should
press the OK-button every time passing a resonance range in order to tag where the range
starts and ends.
If everything is fine the Prohibit frequency range parameters (in Prohibited Frequencies menu)
are provided with right information. If there is a different amount of tags during ramp-up com-
pared to ramp-down nothing will be done but an info message is shown. The same will happen
if the bands are not reasonable.
18
RTC timer 2 control
Time channel 2 is used.
19
RTC timer 3 control
Time channel 3 is used.
20
FB Control WordB.13
21
FB Control WordB.14
22
FB Control WordB.15
23
PID1 in Sleep mode
24
Reserved
25
PID1 supervision limits
PID1 feedback value is beyond supervision limits.
26
PID2 supervision limits
PID2 feedback value is beyond supervision limits.
27
Motor 1 control
Contactor control for
Multi-pump
function
28
Motor 2 control
Contactor control for
Multi-pump
function
29
Motor 3 control
Contactor control for
Multi-pump
function
30
Motor 4 control
Contactor control for
Multi-pump
function
31
Reserved
(Always open)
32
Reserved
(Always open)
33
Reserved
(Always open)
34
Maintenance warning
35
Maintenance fault
Selection
Selection name
Description