HVAC A
PPLICATION
EXAMPLE OF THE INTERLOCK LOGIC:
If the motor starting order is
1
->
2
->
3
->
4
->
5
Now, the interlock of motor
3
is removed, i.e. the value of parameter M3.5.1.27 is set to FALSE,
the order changes to:
1
->
2
->
4
->
5
.
If motor
3
is taken into use again (changing the value of parameter M3.5.1.27 to TRUE) the
system runs on without stopping and motor
3
is placed last in the sequence:
1
->
2
->
4
->
5
->
3
As soon as the system is stopped or goes to sleep mode for the next time, the sequence is
updated to its original order.
1
->
2
->
3
->
4
->
5
M3.14.3
I
NCLUDE
FC
WIRING
There are two different ways to make the connections depending on whether selection
0
or
1
is set as parameter value.
Selection 0, Disabled:
The drive or the regulating motor is not included in the autochange or interlocks logic. The drive
is directly connected to motor 1 as in Figure 25 below. The other motors are auxiliary ones con-
nected to the mains by contactors and controlled by relays in the drive.
Selection
Selection name
Description
0
Disabled
Motor 1 (motor connected to drive) is always frequency
controlled and not affected by interlocks.
1
Enabled
All motors can be controlled and are affected by inter-
locks.