Honeywell
• 29
P
OWER
CABLING
Figure 24.
Tightening torques of cable terminals:
Table 11. Tightening torques of terminals
7
Connect the stripped cables (see Figure 17 and Table 10) as shown in
Figure 24.
•
Expose the shield of all three cables in order to make a 360-degree con-
nection with the cable clamp (1).
•
Connect the (phase) conductors of the supply, brake and motor cables
into their respective terminals (2).
•
Form the rest of the cable shield of all three cables into “pigtails” and make
a grounding connection with a clamp as shown in Figure 24 (3).
Make the pigtails
just long enough
to reach and be fixed to the terminal -
not longer.
Frame
Type
Tightening torque
[Nm]/[lb-in.]
Power and motor
terminals
Tightening torque
[Nm]/[lb-in.]
EMC grounding
clamps
Tightening torque,
[Nm]/[lb-in.]
Grounding terminals
[Nm]
lb-in.
[Nm]
lb-in.
[Nm]
lb-in.
MR4
C 0015—C 0075 0.5—0.6 4.5—5.3
1.5
13.3
2.0
17.7
MR5
C 0100—C 0200 1.2—1.5 10.6—13.3 1.5
13.3
2.0
17.7
MR6
C 0250—C 0400 10
88.5
1.5
13.3
2.0
17.7
MR7
C 0500—C 0750 8/15
*
*. Cable clamping (Ouneva Pressure Terminal Connector)
70.8/132.8* 1.5
13.3
8/15*
70.8/132.8*
1
2
3
3