Honeywell
• 35
HVAC A
PPLICATION
3.5.4
Group 3.2: Start/Stop setup
Table 24. Start/Stop Setup menu
Code
Parameter
Min
Max
Unit
Default
ID
Description
M3.2.1
Remote control
place
0
1
0
172
Selection of remote control
place (start/stop). Can be
used to change back to
remote control from PC
e.g. in case of a broken
panel.
0=I/O control
1=Fieldbus control
M3.2.2
Local/Remote
0
1
0
211
Switch between local and
remote control places
0=Remote
1=Local
M3.2.3
Keypad stop button
0
1
0
114
0=Stop button always
enabled (Yes)
1=Limited function of Stop
button (No)
M3.2.4
Start function
0
1
0
505
0=Ramping
1=Flying start
M3.2.5
Stop function
0
1
0
506
0=Coasting
1=Ramping
M3.2.6
I/O A start/stop
logic
0
3
0
300
CtrlSgn 1
0=Start fwd
1=Start fwd pulse(3-wire)
2=Start fwd pulse
3=AI1 threshold
CrtlSgn 2
0=Start fwd
1=Stop pulse (3-wire)
2=Start fwd pulse
3=AI1 threshold
M3.2.7
I/O B start/stop
logic
0
3
0
363 See above.
M3.2.8
AI1 start threshold
3.00
100.00
%
5.00
185
If M3.2.6 (I/O Start/Stop
Logic) is set to value 3 (AI1
threshold) the motor will
start at the level set with
parameter this parameter
and stop at the same -2%
AI1 can also be used as
frequency reference at the
same time.
M3.2.9
Fieldbus start logic
0
1
1
889
0=Rising edge required
1=State
M3.2.10
Keypad Master
Stop
0
1
1
1806
0=Disable
1=Enable