Honeywell
• 19
M
OUNTING
Note that if several units are mounted above one another the required free
space equals C + D (see Figure 15.). Moreover, the outlet air used for cooling
by the lower unit must be directed away from the air intake of the upper unit.
Figure 15. Installation space when drives are
mounted on top of each other
Table 6. Required cooling air
Type
Cooling air required
[cfm]
MR4
26
MR5
44
MR6
112
MR7
109
MR8
197
MR9
366
C+D